A DC fan is not necessarily a fixed-speed device. Depending on how many wires it has, it can be throttled, monitored, or both. The wire count is the first thing to confirm in any fan specification — here is what each configuration does.

Two-wire: power only

The simplest fan: positive and negative. Speed follows voltage, so the only way to slow it down is to lower the supply voltage or insert a series resistor / thermistor. Two-wire fans are right for cost-driven products with a predictable thermal load, such as adapters and small appliances.

Three-wire: add a tacho (FG)

The third wire is a speed-feedback signal, usually called FG (frequency generator) or tacho. It typically outputs 2 pulses per revolution as an open-collector square wave — so a fan at 3,000 RPM produces a 100 Hz signal your MCU can count. What you get:

  • Verification that the fan is actually spinning (a stalled fan reports zero)
  • Trend monitoring — bearing wear shows up as RPM drift long before failure
  • Closed-loop verification of voltage-based speed control

A tacho tells you the speed but cannot change it. For that you need PWM.

Four-wire: PWM speed control

In the four-wire configuration — the same one used by standard PC and server fans — the fan is fed full voltage on two wires and receives a PWM signal on a dedicated control wire. Key parameters to align with your design:

  • Duty cycle range: typically 20–100%; below the minimum duty the fan may stop, so define your floor
  • PWM frequency: 21–28 kHz is the industry standard — above audible range, so the fan never whines
  • Logic level: 3.3 V or 5 V logic, open-collector or push-pull — confirm with the fan maker
  • Zero-RPM option: some of our models support a "stop at 0% duty" mode for silent standby

PWM control in the fan (rather than voltage control in your circuit) keeps the fan's internal driver at optimal efficiency and gives a clean, linear speed curve — which is why it is the default choice for EV chargers, energy-storage systems and telecom power.

RD: the alarm variant

An RD (rotation detect) signal is a status line rather than a pulse train: it holds one level while the fan rotates and flips when the fan stalls or drops below a threshold speed. Where FG is for logging and trend analysis, RD is for protection circuits — trigger a shutdown or an alarm relay when RD changes. Many of our industrial models can supply RD instead of FG on request.

ConfigurationWiresControlMonitoringTypical use
Basic2Voltage onlyNoneAdapters, appliances
Tacho3Voltage onlyRPM (FG)Servers, medical, monitoring systems
PWM4PWM dutyOptional FG/RDEV chargers, energy storage, telecom

Wiring and connector notes

We build fans with the common harness standards — JST XH2.54 / PH2.0 / VH3.96 and Molex 2510 — and match the wire-color conventions your system already uses. When requesting a quote, send your connector part number and wire-definition table; if you don't have one, a photo of your current fan's plug is enough for us to match it.

Rule of thumb: if the product has a user-facing noise target or a fan-failure alarm requirement, specify PWM + FG from the start — retrofitting signal wires into a two-wire design later costs far more.